In high-voltage power systems, SF6 circuit breakers are core equipment in substations, and their stable operation depends on excellent insulation and arc-extinguishing performance. The pressure of SF6 gas is a key parameter that determines these two performance characteristics.

Abnormal pressure can directly lead to equipment performance degradation, causing serious faults such as insulation breakdown and arc-extinguishing failure, posing a threat to grid safety.

sf6 gas insulation and arc extinguishing principle
sf6 gas insulation and arc extinguishing principle

I. Core Functions of SF6 Gas in Circuit Breakers

SF6 (sulfur hexafluoride), as an inert gas, plays a key role in both insulation and arc extinguishing, with its performance closely related to pressure (non-linear relationship):

First, for insulation, the insulating strength of pure SF6 is 3-5 times that of air, and at rated pressure, it can effectively isolate high-voltage conductors from the grounded casing, preventing discharge at the opened contacts.

Second, for arc extinguishing, its molecules have a very high electron affinity, allowing it to quickly absorb free electrons from the arc; the higher the gas pressure, the faster the arc extinguishing speed, and the stronger the circuit breaker’s current interrupting capability.

sf6 circuit breaker low pressure alarm and leakage fault schematic
sf6 circuit breaker low pressure alarm and leakage fault schematic

II. Low Pressure: Fatal Attenuation of Circuit Breaker Performance

When the pressure is below the rated value (especially the locking pressure), it is a common abnormality that directly leads to core performance failure. At the insulation level, when the pressure drops below 80% of the rated value, the insulation capability sharply decreases.

For example, if the pressure of a 110kV GIS device falls below 0.3MPa (rated 0.4–0.5MPa), it can easily cause contact flashover, condensation and aging of insulation components, creating a vicious cycle. At the arc-extinguishing level, insufficient gas pressure prolongs the arc extinction time, leading to contact burning and damage to the arc-extinguishing chamber. In severe cases, tripping under load can cause equipment explosions.

sf6 gas pressure
sf6 gas pressure

III. High Pressure: Easily Overlooked Hidden Hazards

Excessive pressure does not mean greater safety; on the contrary, it can create multiple hidden hazards:

First, it increases the burden on the sealing system. If the pressure exceeds the withstand capacity of the seals, it accelerates the deformation and aging of the gaskets. In high-temperature environments, pressure rises further, sharply increasing the risk of leakage.

Second, it can cause gas liquefaction. Excessive filling pressure raises the liquefaction temperature. For example, if a rated 0.6 MPa arc-extinguishing chamber is filled to 0.8 MPa, partial liquefaction may occur in winter low temperatures, and liquid SF6 completely loses its insulation and arc-extinguishing capability.

Third, it leads to excessive mechanical stress. Long-term high pressure can cause component damage, such as porcelain bushing cracking and deformation of the arc-extinguishing chamber housing.

sf6 gas
sf6 gas

To ensure circuit breaker performance, pressure control requires three key measures: regular monitoring with density relays (temperature-compensated) for real-time pressure tracking and abnormal alarms; standardized inflation per nameplate rating with 24-hour standing re-inspection; and regular leakage detection via quantitative detectors, replacing aging seals promptly.

Xizi Energy is a Barometer manufacturer in China, specializing in precision barometers designed for medium and high voltage switchgear, SF6 load break switches, and gas‑insulated equipment.

Professional Medium & High Voltage Electrical Equipment Manufacturer

No content is added yet.

Request a Call Back

Let’s talk about your project needs.
Submit your details, and one of our engineers or sales representatives will contact you soon to discuss how Xizi Energy can support your power distribution goals.

Iran, Brazil: +86 18878879777

Turkey, Russia: +86 18823198500

Contact Us Now!

No content is added yet.

Related Blog

SF6-free RMU vs SF6 RMU comparison, showing conventional SF6 ring main unit and modern SF6-free ring main unit for medium voltage distribution

SF6-Free RMU vs SF6 RMU: Key Differences, Pros, Cons & Lifecycle Cost

When selecting medium-voltage ring main units for new build or retrofit projects, engineers and procurement teams consistently face one core decision: choosing between an SF6-free …

Technical guide cover: How to select compatible RMU spare parts, field engineer inspecting ring main unit switchgear at substation

How to Select Compatible RMU Spare Parts: A Practical Replacement Guide

Selecting and replacing faulty components for a Ring Main Unit (RMU) is one of the most common yet error-prone tasks in medium-voltage switchgear maintenance. Many …

RMU operating mechanism troubleshooting procedure for ring main unit switchgear fault diagnosis

RMU Operating Mechanism Troubleshooting: 10 Common Faults, Causes & Solutions

RMU Operating Mechanism Troubleshooting: 10 Common Faults, Causes & Solutions Introduction Field‑found failures of Ring Main Unit (RMU) operating mechanisms may introduce unplanned outages and …

Contact Us Now!